Centrifugal Fan

Centrifugal Fan

A high-pressure centrifugal fan engineered for efficient gas conveying, stable airflow, and durable long-term performance in industrial applications.

Share:

Introduction to the Centrifugal Fan

The RWOOL10-1A high-pressure centrifugal fan is primarily designed for conveying high-pressure gases, including air and other non-flammable, non-explosive, non-volatile gases that are harmless to humans and non-corrosive to steel. The conveyed gas must not contain viscous substances, with dust and hard particulate matter not exceeding 150 mg/m³. Gas temperature must not exceed 80°C.

Model:When viewed from one end of the motor, any impeller rotating clockwise is termed a ‘right-hand fan’, denoted by “right”; conversely, any impeller rotating counter-clockwise is termed a ‘left-hand fan’, denoted by ‘left’.

Structure of the Centrifugal Fan

The Model RWOOL10-1A High-Pressure Centrifugal Fan is mainly composed of an impeller, a casing, an air inlet, a motor, a transmission assembly and other components.

Impeller — Composed of 20 blades and a flat rear disk, it is made of steel plate. Undergoing dynamic and static balance calibration as well as overspeed operation tests, it features high efficiency, stable and reliable operation, and excellent aerodynamic performance.

Casing — Fabricated as an integral structure and non-detachable.

Air Inlet — Manufactured as a monolithic structure and installed on one side of the fan. Its cross-section parallel to the axial direction is curved, which is designed to ensure smooth air inflow into the impeller with minimal pressure loss.

Transmission Assembly — Consists of a main shaft, a bearing housing, rolling bearings, and a pulley or coupling.

Performance and Selection

This brochure only provides the performance parameters and characteristic curves of the No. 1A prototype.

RWOOL10  Performance Parameters of No.1A Prototype

Rotational SpeedNO.Flow RateTotal PressureStatic PressureEfficiencyInternal PowerPower RequiredMatching Motor
r/min№m³/hPaPa%kWkWkW
297016756283222690263.983.297.6
28657288702654066.8103.9122.0
310558295722610670.5123.0144.4
412458298632503871.5144.5169.6
514361295722315971.5165.0193.6
616262292302100771.0186.0218.2220
718163283221806570.5202.7237.8

RWOOL10  № 1A Prototype Performance Curve Diagram

curve diagram 1
curve diagram 2

Installation and Operation

Prior to installation, all necessary materials and tools must be prepared. Conduct a comprehensive inspection of all fan components, paying particular attention to the impeller, casing, main shaft, and bearings. Should any damage be detected, it must be rectified. Subsequently, clean the interior of the bearing housing using kerosene.

During the installation process, the following three points must be observed:

  1. To prevent rusting and reduce disassembly difficulties, apply a layer of lubricating oil or machine oil to certain mating surfaces.
  2. When fitting bolts to mating surfaces, if locating pins are present, secure the pins first before tightening the bolts.
  3. Inspect the interior of the casing and other housing components to ensure no tools or foreign objects have fallen in or been left behind.

Installation Requirements:

  1. When installing the fan, the weight of the air ductwork must not be borne by the casing. Align the inlet duct with the impeller according to the drawings to ensure correct axial and radial clearance dimensions, whilst maintaining the horizontal position of the shaft.
  2. When installing the inlet ductwork, the existing bolts on the inlet itself may be utilised for connection.
  3. When the outlet is installed at an angle, rotate the rear plate appropriately to position the nameplate horizontally.
  4. During installation, use a dial indicator and feeler gauge to measure the coaxiality between the fan shaft and motor shaft, as well as the parallelism at both ends of the coupling. The permissible deviation for shaft coaxiality is 0.05mm, and for coupling face parallelism, 0.1mm.
  5. After installation, manually rotate the impeller to verify absence of excessive tightness or scraping. Confirm correct wiring, integrity of safety devices, and clearance around rotating parts or airflow paths. Only commence trial operation after ensuring all personnel have evacuated the vicinity.
  6. Following motor installation, fit pulley or coupling guards. Where no ducting connects to the inlet, install protective netting or alternative safety devices (supplied by the user). All other components shall be installed as per the drawings.

The relationship between the fan shaft rotational speed n and internal power N is as follows:

n₁ / n₂ = ³√(N₁ / N₂)

Therefore, when the motor capacity remains unchanged, the spindle speed should not be altered. Should the spindle speed increase, the motor risks being overloaded and burnt out.

The power rating of the motor supplied with the fan refers to the normal power consumption under specific operating conditions, plus mechanical losses and the necessary reserve capacity. It does not denote the power required when the outlet is fully open. Should the fan operate without connected ductwork at its inlet or outlet, or without external resistance, the motor may also be at risk of burning out. For safety, a valve should be installed in the inlet or outlet ductwork. During start-up, this valve should remain closed. Once operation commences, the valve should be gradually opened until the specified operating conditions are reached, while monitoring the motor current to ensure it does not exceed the rated value.

Maintenance of the Centrifugal Fan

  1. Regularly remove dust, dirt, water, and other impurities from the fan and gas delivery pipes, and prevent rusting.
  2. When repairing the fan, power must be disconnected and the unit stopped first. Under no circumstances should repairs be performed while the unit is running. The switch must be monitored by a designated person to prevent accidental power restoration.
  3. Regularly check the responsiveness of the thermometer and oil gauge.
  4. Replace lubricating oil after each disassembly and repair, and perform regular scheduled oil changes.
  5. Before and after each maintenance session, meticulously record, count, and verify the quantity of tools and raw materials to prevent items from being left inside the fan or piping.
  6. Keep personnel clear of the inlet and outlet areas within ten meters during fan test runs.
  7. Unauthorized personnel are strictly prohibited from observing during installation, maintenance, and test runs.

Fault and Case

The primary faults of fans include:

I. Severe vibration in the bearing housing.

  1. Misalignment between the fan shaft and motor shaft, resulting in coupling skew.
  2. Friction between the casing or inlet and the impeller.
  3. Insufficient rigidity or instability of the foundation.
  4. Loose impeller rivets or deformation of the impeller hub.
  5. Looseness between the impeller hub and shaft, or movement of coupling bolts.
  6. Loose connecting bolts between the casing and bracket, bearing housing and bracket, bearing housing cover and base, etc.
  7. Improper installation of fan inlet/outlet ducts causing vibration.
  8. Rotor imbalance.
  9. Excessively narrow ductwork with high air velocity.

II. Excessive Bearing Temperature Rise.

  1. Severe vibration in the bearing housing.
  2. Poor-quality, degraded, or overfilled lubricating grease containing impurities such as dust, sand particles, or contaminants.
  3. Excessive or insufficient tightening torque of the bearing housing cover and base connecting bolts.
  4. Misalignment between the shaft and rolling bearings, resulting in non-coaxiality between the front and rear bearings.
  5. Damaged rolling bearings.

III. Excessive motor current and overheating

  1. Inlet gate or throttle valve not fully closed during startup.
  2. Flow rate exceeds specified value or air duct leakage.
  3. Gas transported by fan contains viscous substances or ambient temperature is too low, resulting in excessive gas density.
  4. Motor input voltage too low or single-phase power failure.
  5. Misaligned coupling connection, excessively tight belt tension, or uneven belt clearance.
  6. Severe vibration originating from the bearing housing.
  7. Impact from deteriorating performance or malfunction of parallel-connected fans.

IV. Belt slippage

The corresponding grooves on the two pulleys are not properly aligned.

V.Belt jumping

The distance between the two pulleys is too close, or the belt is excessively long.